Measure the hot room, add the glass and stone, and see what size heater the manufacturers' own rules point to. Free, no sign-up.

Units
Inside size of the hot room
Length
ft in
Width
ft in
Ceiling height
ft in
Surfaces with no insulation behind them

Area is width times height. A glass door 2 ft wide and 6 ft tall is 12 sq ft. Leave at 0 if there is none.

Heater

Heater size for this room

Enter the room size

The calculator needs JavaScript. The rules it uses are written out below.

Always confirm with the heater manufacturer and a licensed electrician. This is a rule-of-thumb estimate. It cannot see your insulation, vents, climate or wiring. The manual of the heater you buy has the final say on room volume, clearances, breaker and wire size.

How the size is worked out

The calculator does one piece of arithmetic that every heater manual asks you to do before you buy. All of the numbers come from the heater makers' own guidance. None are ours.

  1. Room volume. Length times width times ceiling height, measured inside the hot room.
  2. Add the cold surfaces. Glass, stone, tile, brick and concrete with no insulation behind them soak up heat. Harvia counts each square meter of such surface as 1.2 m³ of extra room (about 3.9 cu ft for each sq ft). HUUM counts 1 m³.
  3. Log walls. If the inside walls are bare log, Harvia multiplies the room volume by 1.5.
  4. Volume to power. Harvia and HUUM both put the average at 1 kW of heater power for each cubic meter of calculated volume. That is the top of the range shown.
  5. The bottom of the range. Harvia's own worked example sizes a calculated volume of about 8.5 m³ at a minimum of 6 kW. That is the same ratio as the shortcut many North American retailers quote, 1 kW per 50 cu ft. The calculator uses it as the low end.
  6. Wood-burning stoves are sold by the room volume they suit, not by kilowatts, so for a wood stove the result is the calculated volume alone. Harvia's wood stove guide uses the same 1.2 and 1.5 factors.
The published rules this page uses.
RuleFigurePublished by
Power per volume1 kW per m³ (35.3 cu ft)Harvia, HUUM
Glass, stone, tile, brick, concrete+1.2 m³ per m²Harvia
The same, HUUM+1 m³ per m²HUUM (website and DROP manual)
The same, HUUM in North America+4.92 cu ft per sq ft (1.5 m³ per m²)"Sizing Your HUUM" sheet
Bare log wallsroom volume × 1.5Harvia
Low end of the power range1 kW per 50 cu ft (1.416 m³)Retail shortcut; matches Harvia's 8.5 m³ example

Sources

Harvia and HUUM also have their own calculators: Harvia Sauna Calculator and HUUM heater calculator. If you are buying one of their heaters, use theirs as well.

What this page does not know. Insulation quality, vents, outdoor temperature, stone mass and your home's wiring all change the answer. Rules also differ between makers, which is why the page shows a range. Treat the result as a shopping shortlist. Then check the room volume range printed for the exact model, and have a licensed electrician confirm the circuit before anything is installed. Wood stoves also need the clearances and chimney the manual and your local fire code require.

The code is open source under the MIT license, so you can read every rule.